|
The HTS HiStop®
Team's patented high temperature, high pressure (HTHP) HiStops® are used primarily to solve maintenance and engineering problems where operating conditions exceed conventional line stop ranges.
Team's HiStops® can be used to isolate pipes from 1/2" to 16" in size, with temperatures to 1200oF (649oC) and pressures to 2600 psig (179 Bar).
Team has successfully stopped a 6" boiler feedwater line leaking water at the rate of 1650 gpm and flowing at a velocity of 22 ft/sec. Pressure was 2100 psig at 400oF. The company stopped another 6" boiler feedwater line a 2300 psig and 350oF.
Team's advanced HiStop® methods utilize patented techniques and equipment such as the metal-to-metal seal between the plug and the line.
Basic engineering techniques applied to the Team HiStop® includes (A) the installation and pressure testing of a special HiStop® fitting welded to the pipe, the installation of the valve, and the (B) precision cutting and reaming operation to make a tapered hole through the pipe. The pipe is then plugged (C) with a precision-ground, tapered steel plug that provides the seal to the pipe. This permits the depressuring of the system for the necessary maintenance or project work. A completion plug (D) with metal-to-metal seal and O-ring backup to permit HTHP operations is installed in the flange, thus allowing removal of the service valve and completion of the job.
Team's HiStop® applications include the following:
- Valve installation replacement
- Pipe replacement
- Pipe repairs
- Valve repairs
- Decommissioning pipes
- Isolate pressure vessels
- Repair pressure letdown stations
- Rerouting of process flow
- External leaks
Team HiStops® can be applied to the following pipe materials:
- Carbon steel
- Alloy steel
- Stainless steel
- Cast Iron
- Brass/copper
- Concrete lined pipe
- Concrete
- Transite
- Plastic
- Fiberglass
|